Schneider TM3DQ16R

$ 56,00 Request exact price

Terms of sale:

  • Done Price Without Shipping:
    Our prices are listed without shipping costs. Shipping charges will be calculated and added during checkout based on your location and preferred shipping method.
  • Done Price Variability:
    Please note that prices are not fixed and may change due to factors such as market fluctuations, supplier costs, or promotional offers.
  • Done Worldwide Delivery:
    We offer delivery to almost any country worldwide. During checkout, you can select your country for shipping options and associated costs.
  • Check Mark These terms ensure transparency and flexibility in pricing and shipping options for our customers across the globe.
GUARANTEED SAFE CHECKOUT
  • Visa Card
  • MasterCard
  • American Express
  • Discover Card
  • PayPal
Category:

Description

Main
range of productModicon TM3
Product or component typeDiscrete output module
Range compatibilityModicon M241
Modicon M251
Modicon M221
Modicon M262
Discrete output typeRelay normally open
Discrete output number16
Discrete output logicPositive or negative
Discrete output voltage240 V AC for relay output
30 V DC for relay output
Discrete output current2000 mA for relay output
Complementary
Discrete I/O number16
Current consumption0 mA at 24 V DC via bus connector (at state off)
75 mA at 24 V DC via bus connector (at state on)
Response time10 ms (turn-on)
5 ms (turn-off)
Mechanical durability20000000 cycles
Minimum load10 mA at 5 V DC for relay output
Local signalling1 LED per channel (green) for output status
Electrical connection10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for outputs
Maximum cable distance between devicesUnshielded cable: <30 m for relay output
InsulationBetween output and internal logic at 2300 V AC
Between outputs at 750 V AC
Between output groups at 1500 V AC
MarkingCE
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height90 mm
Depth84.6 mm
Width27.4 mm
Net weight0.145 kg
Environment
standardsEN/IEC 61010-2-201
EN/IEC 61131-2
Product certificationsC-Tick
cULus
Resistance to electrostatic discharge8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz…3 GHz conforming to EN/IEC 61000-4-3
Resistance to magnetic fields30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients2 kV for relay output conforming to EN/IEC 61000-4-4
Surge withstand1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC
Resistance to conducted disturbances10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emissionRadiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
Ambient air temperature for operation-10…35 °C vertical installation
-10…55 °C horizontal installation
Ambient air temperature for storage-25…70 °C
Relative humidity10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protectionIP20 with protective cover in place
Pollution degree2
Operating altitude0…2000 m
Storage altitude0…3000 m
Vibration resistance3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel
3 gn at 8.4…150 Hz on panel
Shock resistance15 gn for 11 ms
Packing Units
Unit Type of Package 1Db
Number of Units in Package 11
Package 1 Height7.426 cm
Package 1 Width10.516 cm
Package 1 Length12.583 cm
Package 1 Weight248.9 g
Unit Type of Package 2S04
Number of Units in Package 242
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight12.0 kg