Schneider ATV312HD15N4

$ 1.112,00 Request exact price

Terms of sale:

  • Done Price Without Shipping:
    Our prices are listed without shipping costs. Shipping charges will be calculated and added during checkout based on your location and preferred shipping method.
  • Done Price Variability:
    Please note that prices are not fixed and may change due to factors such as market fluctuations, supplier costs, or promotional offers.
  • Done Worldwide Delivery:
    We offer delivery to almost any country worldwide. During checkout, you can select your country for shipping options and associated costs.
  • Check Mark These terms ensure transparency and flexibility in pricing and shipping options for our customers across the globe.
GUARANTEED SAFE CHECKOUT
  • Visa Card
  • MasterCard
  • American Express
  • Discover Card
  • PayPal
Category:

Description

Main
range of productAltivar 312
Product or component typeVariable speed drive
Product destinationAsynchronous motors
Product specific applicationSimple machine
Assembly styleWith heat sink
Component nameATV312
Motor power kW15 kW
Motor power hp20 hp
[Us] rated supply voltage380…500 V – 15…10 %
Supply frequency50…60 Hz – 5…5 %
Network number of phases3 phases
Line current48.2 A at 380 V, Isc = 22 kA
36.8 A at 500 V
EMC filterIntegrated
Apparent power32 kVA
Maximum transient current49.5 A for 60 s
Power dissipation in W492 W at nominal load
Speed range1…50
Asynchronous motor control profileSensorless flux vector control with PWM type motor control signal
Factory set : constant torque
Electrical connectionAl1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1…LI6 terminal 2.5 mm² AWG 14
L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 25 mm² AWG 3
SupplyInternal supply for logic inputs: 19…30 V 100 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (2.2 to 10 kOhm): 10…10.8 V 10 mA, protection type: overload and short-circuit protection
communication port protocolModbus
CANopen
IP degree of protectionIP20 on upper part without cover plate
IP21 on connection terminals
IP31 on upper part
IP41 on upper part
Option cardCommunication card for CANopen daisy chain
Communication card for DeviceNet
Communication card for Fipio
Communication card for Modbus TCP
Communication card for Profibus DP
Complementary
Supply voltage limits323…550 V
Prospective line Isc22 kA
Continuous output current33 A at 4 kHz
Output frequency0…500 Hz
Nominal switching frequency4 kHz
Switching frequency2…16 kHz adjustable
Transient overtorque170…200 % of nominal motor torque
Braking torque150 % during 60 s with braking resistor
100 % with braking resistor continuously
150 % without braking resistor
Regulation loopFrequency PI regulator
Motor slip compensationAdjustable
Automatic whatever the load
Suppressable
Output voltage<= power supply voltage
Tightening torqueAl1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1…LI6: 0.6 N.m
L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 4.5 N.m
InsulationElectrical between power and control
Analogue input number3
Analogue input typeAI1 configurable voltage 0…10 V, input voltage 30 V max, impedance: 30000 Ohm
AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm
AI3 configurable current 0…20 mA, impedance: 250 Ohm
Sampling durationAI1, AI2, AI3: 8 ms analog
LI1…LI6: 4 ms discrete
Response timeAOV, AOC 8 ms for analog
R1A, R1B, R1C, R2A, R2B 8 ms for discrete
Linearity error+/- 0.2 % for output
Analogue output number1
Analogue output typeAOC configurable current: 0…20 mA, impedance: 800 Ohm, resolution: 8 bits
AOV configurable voltage: 0…10 V, impedance: 470 Ohm, resolution: 8 bits
Discrete input logicLogic input not wired (LI1…LI4), < 13 V (state 1)
Negative logic (source) (LI1…LI6), > 19 V (state 0)
Positive logic (source) (LI1…LI6), < 5 V (state 0), > 11 V (state 1)
Discrete output number2
Discrete output typeConfigurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC – 100000 cycles
Configurable relay logic: (R2A, R2B) NC – 100000 cycles
Minimum switching currentR1-R2 10 mA at 5 V DC
Maximum switching currentR1-R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms
R1-R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms
R1-R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms
R1-R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms
Discrete input number6
Discrete input type(LI1…LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm
Acceleration and deceleration rampsS, U or customized
Linear adjustable separately from 0.1 to 999.9 s
Braking to standstillBy DC injection
Protection typeInput phase breaks: drive
Line supply overvoltage and undervoltage safety circuits: drive
Line supply phase loss safety function, for three phases supply: drive
Motor phase breaks: drive
Overcurrent between output phases and earth (on power up only): drive
Overheating protection: drive
Short-circuit between motor phases: drive
Thermal protection: motor
Insulation resistance>= 500 mOhm 500 V DC for 1 minute
Local signalling1 LED (red) for drive voltage
Four 7-segment display units for CANopen bus status
Time constant5 ms for reference change
Frequency resolutionAnalog input: 0.1…100 Hz
Display unit: 0.1 Hz
Connector type1 RJ45 for Modbus/CANopen
physical interfaceRS485 multidrop serial link
Transmission frameRTU
Transmission rate10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen
4800, 9600 or 19200 bps for Modbus
Number of addresses1…127 for CANopen
1…247 for Modbus
Number of drive127 for CANopen
31 for Modbus
MarkingCE
operating positionVertical +/- 10 degree
Outer dimension390 x 245 x 190 mm
595 x 234 x 268 mm
330 x 245 x 190 mm
Height329.5 mm
Width245 mm
Depth192 mm
Net weight11 kg
Environment
Dielectric strength2410 V DC between earth and power terminals
3400 V AC between control and power terminals
Electromagnetic compatibility1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
standardsIEC 61800-5-1
IEC 61800-3
Product certificationsUL
CSA
DNV
GOST
C-Tick
NOM
Pollution degree2
Protective treatmentTC
Vibration resistance1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance15 gn for 11 ms conforming to EN/IEC 60068-2-27
Relative humidity5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for storage-25…70 °C
Ambient air temperature for operation-10…50 °C without derating (with protective cover on top of the drive)
-10…60 °C with derating factor (without protective cover on top of the drive)
Operating altitude<= 1000 m without derating
1000…3000 m with current derating 1 % per 100 m
Packing Units
Unit Type of Package 1Db
Number of Units in Package 11
Package 1 Height28.0 cm
Package 1 Width29.0 cm
Package 1 Length40.0 cm
Package 1 Weight11.856 kg
Unit Type of Package 2P06
Number of Units in Package 24
Package 2 Height80.0 cm
Package 2 Width80.0 cm
Package 2 Length60.0 cm
Package 2 Weight59.82 kg
Contractual warranty
Warranty18 months