Start with torque control (current limited to 3.5 In)
IcL starter rating
140 A connection in the motor supply line for standard applications
IP degree of protection
IP00
Complementary
Assembly style
With heat sink
Function available
Internal bypass
Supply voltage limits
195…484 V
Supply frequency
50…60 Hz – 10…10 %
Network frequency
45…66 Hz
Device connection
In the motor supply line
To the motor delta terminals
[Uc] control circuit voltage
230 V – 15…10 % 50/60 Hz
Control circuit consumption
20 W
Discrete output number
2
Discrete output type
Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Minimum switching current
100 mA 12 V DC relay outputs)
Maximum switching current
5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs
Discrete input number
3
Discrete input type
LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Discrete input voltage
24 V <= 30 V
Discrete input logic
Positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA
Output current
0.4…1 Icl adjustable
PTC probe input
750 Ohm
communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure line
Thermal protection motor
Thermal protection starter
Marking
CE
Type of cooling
Forced convection
operating position
Vertical +/- 10 degree
Height
14.02 in (356 mm)
Width
5.91 in (150 mm)
Depth
9.04 in (229.5 mm)
Net weight
39.68 lb(US) (18 kg)
Motor power range AC-3
30…50 kW 200…240 V 3 phases
55…100 kW 380…440 V 3 phases