40 mA at 5 V DC via bus connector (at state on)
5 mA at 5 V DC via bus connector (at state off)
0 mA at 24 V DC via bus connector (at state on)
0 mA at 24 V DC via bus connector (at state off)
Discrete input voltage type
DC
Voltage state 1 guaranteed
15…28.8 V for input
Current state 1 guaranteed
>= 2.5 mA (input)
Voltage state 0 guaranteed
0…5 V for input
Current state 0 guaranteed
<= 1 mA (input)
Input impedance
3.4 kOhm
Response time
4 ms (turn-on)
4 ms (turn-off)
Local signalling
1 LED per channel (green) for input status
Electrical connection
10 x 1.5 mm² removable spring terminal block with pitch 3.81 mm adjustment for inputs
Maximum cable distance between devices
Unshielded cable: <50 m for regular input
Insulation
Between input and internal logic at 500 V AC
Non-insulated between inputs
Marking
CE
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height
90 mm
Depth
84.6 mm
Width
27.4 mm
Net weight
0.1 kg
Environment
standards
EN/IEC 61131-2
EN/IEC 61010-2-201
Product certifications
C-Tick
cULus
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields
10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz…3 GHz conforming to EN/IEC 61000-4-3
Resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients
1 kV for I/O conforming to EN/IEC 61000-4-4
Surge withstand
1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC
Resistance to conducted disturbances
10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
Ambient air temperature for operation
-10…35 °C vertical installation
-10…55 °C horizontal installation
Ambient air temperature for storage
-25…70 °C
Relative humidity
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection
IP20 with protective cover in place
Pollution degree
2
Operating altitude
0…2000 m
Storage altitude
0…3000 m
Vibration resistance
3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel
3 gn at 8.4…150 Hz on panel